Evaluasi dampak perkuatan gedung eksisting berdasarkan level kinerja struktur (Studi Kasus : Concrete Jacketing Kolom Gedung Rumah Sakit X di Yogyakarta)
Date
2024-07-26Author
Rohman, Wahyu Nur
Marasabessy, Muhammad Irfan
Alhamid, Muhamad Fadlan
Hidayat, Muhammad Zakki Rizal
Putri, Mayangsari Rafiqa
Hanafi, Nufrizal Faried
Metadata
Show full item recordAbstract
Hospital building X, with 3 floors in Yogyakarta, was constructed in
stages. The first phase involved erecting one floor, as planned according
to SNI 1726 2012. Six years later, the next phase commenced. However,
with the enactment of SNI 1726 2019, an evaluation was necessary. The
result indicated that the existing building columns were unsafe,
necessitating reinforcement and structural adjustment. Column
reinforcement was done using the concrete jacketing method. The new
structure altered the number of required reinforcements. The research
aimed to assess the building's structural performance and the plastic
hinge plasticity level before and after reinforcement. Licensed ETABS
software was used for nonlinear pushover analysis. The modeling was
divided into two parts: without and with reinforcement. The research
findings showed a decrease in target displacement during BSE-2N
earthquakes before and after reinforcement. The average reduction in
both x and y directions was 23.85%, with consistent performance
categorized as damage control. Similarly, target displacement during
BSE-1N earthquakes decreased before and after reinforcement, with an
average reduction of 23.35% in both directions. Consequently, the
performance target improved from damage control to immediate
occupancy. The plastic hinge plasticity level before and after
reinforcement during BSE-1N earthquakes remained consistent,
categorized as B-C. The average decrease in the number of plastic hinges
in both x and y directions at the BSE-1N earthquake level was 36.45%.